•Light Duty (DFE-30 – DFE-38) AC53b: 3-5: 355
•Core Duty DFE-30 – DFE-38) AC53b: 3.5-12: 1188
•Start Time: 0.5 to 30 Seconds
•Stop Time: 0 to 30 Seconds
•Soft Start/Stop Control: 24V DC/110V AC galvanically isolated terminals A1-A2
VAuxiliary Circuits (Relays): Run - 13/14, Ready - 23/24. 230VAC 3A, Ac11
•Indication: Multifunction LED on the front of the unit
•Power Terminals: Input 1/L1, 3/L2 and 5/L3
VOutput 2/T1, 4/T2 and 6/T3
•Up to 55kW IP20 rated wire
•clamping terminals
•75kW to 280kW External Busbars
•IP Rating: Up to 55kW IP20 75kW to 280kW IP00
•Ambient Temperature: 0°C to 40°C
•Above 40°C de-rate linearly by 2% of unit FLC per °C to a de-rate of 40% at 60°C
•Transport and Storage: -25°C to +60°C
•Altitude: 1000m Above 1000m de-rate linearly by 1% of unit FLC per 100m to a maximum altitude of 2000m
•Humidity: Max. 85% non-condensing, not exceeding 50% at 40°C
Manufacturer | Motortronics |
---|